NACSI AC Panels have been certified as exceeding National Building Code of Canada requirements in the following categories; 

ASTM C 1363 – 05 : Thermal Performance (R- values) at R20 Benchmark

AC Panel 3” 21% Superior Efficiency
AC Panel 6” 42% Superior Efficiency



ASTM D 6416/D 6416M – 01(2007) : Uniformly Distributed Load (UDL Loading)    

AC Panel 4' x 10' x 6” -   UDL loading with panel loading length of 109"

UDL Load Total load Deflection
61 lbs/ft2     (2.92 kN/m2) 4433lbs (19.7 kN) 3/32" (2.4 mm)
81.4 lbslft2     (3.90 kN/m2) 5915lbs (26.3 kN) 9/64" (3.6 mm)
91,8 lbs/ft2     (4.40 kNlm2) 6671 lbs (29.7 kN) 7/32" (5.4 mm)
102.2 lbs/ft2     (4.89 kN/m2) 7427 lbs (33.0 kN) 15/64" (6.0 mm)


The allowable deflection for the 109" panel to meet NBC Snow load Requirements would be
109/360= 0.3" (5/16") (7.6mm) > than any result noted above


ASTM D 3043 - 00 : "Standard Test Method for Testing Structural Panels in Flexure ( Method B,)"

 AC Panel 4' x 10' x 6” -  Two point load with panel loading length of 90.25"

Load Deflection
Two 486 pound loads 28" apart 0.125"    **
(Two 220.5 kilogram loads 71Omm apart) 3.2 mm


The allowable deflection for the 90.25" panel would be
90.251360= 0,25" (1/8") (6.35mm) > than any results noted above

Translating this value ** to wind loads, AC Panel is capable of sustaining wind loads of 7.33 kPa.

The highest wind loads in Canada as per NBC tables is 1.41 kPa  (29.44 lbs/ft^2) for Resolute Bay at 1/100 occurrences.


Results of independent testing indicate that the NACSI AC Panel can support unprecedented free span and compression loads with deflections well within the standards of the NBC of Canada.

NACSI AC Panels are certified for Foundation, Wall, Floor and Roof applications